Conductor sizing

Voltage drop calculator

Estimate voltage drop, percent drop, and end voltage for any run — copper or aluminum, single- or three-phase — and size the conductor to NEC's 3% branch and 5% combined guidance.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

Method

The estimate uses the single-conductor formula Vdrop = K × length × current × (R ÷ 1000). K is 2 for single-phase and √3 (about 1.732) for three-phase. R is the conductor's DC resistance in ohms per 1000 ft, taken from NEC Chapter 9, Table 8 for uncoated copper and aluminum. Percent drop is the drop divided by the source voltage.

NEC 3% / 5% guidance

The NEC suggests (informational note, not a hard rule) a branch circuit stay at or below 3% and the feeder plus branch stay at or below 5%. The calculator flags both. When a run exceeds 3%, it suggests the thinnest conductor that brings it back under 3% so you don't over-buy copper.

NEC voltage drop calculations: what the code actually requires

The NEC does not set a general, enforceable voltage-drop limit for branch circuits or feeders. The familiar 3% and 5% figures come from Informational Notes — notably NEC 210.19(A) Informational Note No. 4, which recommends limiting branch-circuit drop to 3% and combined feeder-plus-branch drop to 5%. Informational notes are advisory, not enforceable requirements. A few cases do carry mandatory limits, such as fire pump circuits and sensitive electronic equipment under Article 647, and some local jurisdictions and energy codes adopt the 3%/5% guidance as a hard requirement — so check with your AHJ. In practice, treat 3%/5% as the design target: run this calculator for your length, load, and conductor, and if the drop comes in high, step up a wire size.

Based on NEC Ch.9 Table 8 (DC resistance, ~75°C, uncoated conductors).

FAQ

How is voltage drop calculated?

Voltage drop = K × length (ft) × current (A) × (R ÷ 1000), where K is 2 for single-phase or √3 for three-phase, and R is the conductor's DC resistance in ohms per 1000 ft. Percent drop is the voltage drop divided by the source voltage, times 100.

What voltage drop does the NEC allow?

The NEC's informational notes recommend keeping a branch circuit at or below 3% and the feeder plus branch combined at or below 5%. These are recommendations (FPN), not enforceable rules, but most designers and inspectors treat 3% as the practical target.

Does copper or aluminum drop more voltage?

For the same size, aluminum has higher resistance than copper, so it drops more voltage. To carry the same load over the same distance with a similar drop, aluminum usually needs to be one or two sizes larger than copper.

Is the NEC 3% voltage drop rule mandatory?

In most cases, no. The 3% branch-circuit and 5% combined figures live in NEC Informational Notes (such as 210.19(A) Informational Note No. 4), which are advisory rather than enforceable code. There are exceptions: fire pump circuits have enforceable requirements, and sensitive electronic equipment under Article 647 has a mandatory voltage-drop limit. Some local jurisdictions and energy codes also adopt the 3%/5% guidance as a binding rule, and the authority having jurisdiction (AHJ) has the final say — so confirm locally. Even where it is optional, staying at or under roughly 3% is a sensible target: excessive drop wastes energy and can mean dim lights, sluggish motors, and nuisance tripping.

How do I do an NEC voltage drop calculation by hand?

A common shortcut for single-phase circuits is VD = 2 × K × I × L / CM, where K is roughly 12.9 ohm-cmil/ft for copper at 75°C (about 21.2 for aluminum), I is the load current in amps, L is the one-way run length in feet, and CM is the conductor's circular-mil area. For three-phase, replace the 2 with 1.732. Alternatively, use the approach this calculator takes: pull the conductor's resistance from NEC Chapter 9 Table 8 (ohms per 1,000 ft) and compute VD = 2 × R × I × L / 1,000 (again swapping 2 for 1.732 on three-phase). Both are estimates; actual drop varies with temperature, power factor, and terminations. Divide VD by the source voltage and multiply by 100, then check the percentage against the 3%/5% guidance.

What does this calculator not include?

It estimates voltage drop only, using NEC Chapter 9 Table 8 DC resistance. It does not size for ampacity, temperature derating, conduit fill, power factor, or continuous-load factors, and it is not a substitute for a licensed electrician or your local code (AHJ).

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. This is not a substitute for a licensed electrician or your local code (AHJ). It does not fully model ampacity, temperature derating, power factor, or continuous-load factors. Always verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.