Method
The estimate uses the single-conductor formula
Vdrop = K × length × current × (R ÷ 1000). K is 2 for
single-phase and √3 (about 1.732) for three-phase. R is the conductor's DC resistance in
ohms per 1000 ft, taken from NEC Chapter 9, Table 8 for uncoated copper
and aluminum. Percent drop is the drop divided by the source voltage.
NEC 3% / 5% guidance
The NEC suggests (informational note, not a hard rule) a branch circuit stay at or below
3% and the feeder plus branch stay at or below 5%. The calculator flags both. When a run
exceeds 3%, it suggests the thinnest conductor that brings it back under 3% so you don't
over-buy copper.
NEC voltage drop calculations: what the code actually requires
The NEC does not set a general, enforceable voltage-drop limit for branch circuits or
feeders. The familiar 3% and 5% figures come from Informational Notes — notably NEC
210.19(A) Informational Note No. 4, which recommends limiting branch-circuit drop to 3%
and combined feeder-plus-branch drop to 5%. Informational notes are advisory, not
enforceable requirements. A few cases do carry mandatory limits, such as fire pump
circuits and sensitive electronic equipment under Article 647, and some local
jurisdictions and energy codes adopt the 3%/5% guidance as a hard requirement — so check
with your AHJ. In practice, treat 3%/5% as the design target: run this calculator for
your length, load, and conductor, and if the drop comes in high, step up a wire size.
Based on NEC Ch.9 Table 8 (DC resistance, ~75°C, uncoated conductors).