Voltage drop scenario

Wire size for 100 amps at 100 feet

At 240 V single-phase, copper 4 AWG keeps a 100 amps load at about 2.57% drop over 100 feet — within the 3% design target used here. Adjust material, voltage, or phase below.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

100 amps at 100 feet: the short answer

At 240 V single-phase over 100 feet, a 100 amps load needs copper 4 AWG to stay near 2.57% — inside the 3% design target used for this comparison. For comparison, copper 12 AWG would drop about 38.60 V (16.08%) on the same run.

Before you pull wire

This is a voltage-drop estimate only. The conductor must also meet ampacity, temperature derating, and overcurrent rules — use the larger of the voltage-drop size and the ampacity size. Aluminum of the same size drops more, so it usually needs to go up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Sized for voltage drop using NEC Ch.9 Table 8 DC resistance. The 3% figure is a common design target from informational guidance, not a substitute for a code review.

Where this 100 amps, 100 feet scenario fits

A 100 A, 100-foot run is usually feeder or subpanel territory rather than an ordinary branch circuit. It may serve a detached garage, workshop, addition, or other distribution point, which brings grounding, disconnect, load calculation, and feeder rules beyond simple voltage drop.

This page deliberately uses a conservative 3% design target so conductor choices can be compared on equal terms. NEC voltage-drop language is generally informational, and feeder-plus-branch performance must be considered together. Treat the result as one input to a feeder design, not as a complete 100 A feeder specification.

Distance changes the conductor decision

Copper recommendations for a 100 amps load at 240 V single-phase, using the same 3% target
One-way distance Suggested copper size Calculated drop
50 ft 6 AWG 2.05%
100 ft 4 AWG 2.57%
150 ft 2 AWG 2.43%
200 ft 1 AWG 2.57%

Checks specific to this project

  • Complete a load calculation instead of assuming the feeder will continuously carry 100 A.
  • Check feeder conductor, neutral, equipment-grounding conductor, and disconnect requirements separately.
  • Review whether dwelling-service or feeder allowances apply; this calculator does not apply them.
  • Have the conductor and equipment terminations checked for material, temperature rating, and physical size.

FAQ

What wire size do I need for 100 amps at 100 feet?

For voltage drop at 240 V single-phase, copper 4 AWG keeps a 100 amps load near 2.57% over 100 feet, meeting the 3% design target used on this page. Ampacity, derating, equipment instructions, and local code may require a different size — confirm with a licensed electrician.

How much voltage drop does 100 amps over 100 feet have?

On a baseline copper 12 AWG at 240 V single-phase, 100 amps over 100 feet drops about 38.60 V (16.08%). Larger conductors drop less; the calculator shows the exact figure for any size.

Is this voltage-drop sizing the same as ampacity sizing?

No. This page sizes for voltage drop only, using NEC Chapter 9 Table 8 DC resistance. The conductor must also satisfy ampacity, temperature derating, and overcurrent-protection rules. Use the larger of the voltage-drop size and the ampacity size, and verify with your local code (AHJ).

Sources & verification

Source links and page assumptions reviewed .

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. Not a substitute for a licensed electrician or your local code (AHJ). Voltage-drop sizing does not replace ampacity, temperature derating, power factor, or continuous-load checks. Verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.