Voltage drop scenario

Wire size for 50 amps at 200 feet

At 240 V single-phase, copper 4 AWG keeps a 50 amps load at about 2.57% drop over 200 feet — within the 3% design target used here. Adjust material, voltage, or phase below.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

50 amps at 200 feet: the short answer

At 240 V single-phase over 200 feet, a 50 amps load needs copper 4 AWG to stay near 2.57% — inside the 3% design target used for this comparison. For comparison, copper 12 AWG would drop about 38.60 V (16.08%) on the same run.

Before you pull wire

This is a voltage-drop estimate only. The conductor must also meet ampacity, temperature derating, and overcurrent rules — use the larger of the voltage-drop size and the ampacity size. Aluminum of the same size drops more, so it usually needs to go up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Sized for voltage drop using NEC Ch.9 Table 8 DC resistance. The 3% figure is a common design target from informational guidance, not a substitute for a code review.

Where this 50 amps, 200 feet scenario fits

Two hundred feet turns a familiar 50 A circuit into a long-run project. It may represent an outbuilding, remote equipment pad, gate, pump, or distant charging location where conductor cost and voltage performance both matter.

This is the point where alternatives deserve a written comparison: a larger conductor, a different equipment location, a feeder with a local subpanel, or a revised load. The cheapest conductor that carries current may not deliver acceptable voltage at the far end, especially when equipment has motors or electronics.

Distance changes the conductor decision

Copper recommendations for a 50 amps load at 240 V single-phase, using the same 3% target
One-way distance Suggested copper size Calculated drop
50 ft 10 AWG 2.52%
100 ft 6 AWG 2.05%
150 ft 4 AWG 1.93%
200 ft 4 AWG 2.57%

Checks specific to this project

  • Recheck the route before ordering; a 10% length error is 20 feet on this scenario.
  • Model the real operating current as well as the maximum possible current.
  • Have a professional evaluate fault-current, grounding, disconnect, and feeder requirements for remote structures.
  • Use pulling tension, conduit fill, and termination size as constructability checks for any larger conductor.

FAQ

What wire size do I need for 50 amps at 200 feet?

For voltage drop at 240 V single-phase, copper 4 AWG keeps a 50 amps load near 2.57% over 200 feet, meeting the 3% design target used on this page. Ampacity, derating, equipment instructions, and local code may require a different size — confirm with a licensed electrician.

How much voltage drop does 50 amps over 200 feet have?

On a baseline copper 12 AWG at 240 V single-phase, 50 amps over 200 feet drops about 38.60 V (16.08%). Larger conductors drop less; the calculator shows the exact figure for any size.

Is this voltage-drop sizing the same as ampacity sizing?

No. This page sizes for voltage drop only, using NEC Chapter 9 Table 8 DC resistance. The conductor must also satisfy ampacity, temperature derating, and overcurrent-protection rules. Use the larger of the voltage-drop size and the ampacity size, and verify with your local code (AHJ).

Sources & verification

Source links and page assumptions reviewed .

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. Not a substitute for a licensed electrician or your local code (AHJ). Voltage-drop sizing does not replace ampacity, temperature derating, power factor, or continuous-load checks. Verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.