Voltage drop scenario

Wire size for 20 amps at 100 feet

At 240 V single-phase, copper 10 AWG keeps a 20 amps load at about 2.02% drop over 100 feet — within the 3% design target used here. Adjust material, voltage, or phase below.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

20 amps at 100 feet: the short answer

At 240 V single-phase over 100 feet, a 20 amps load needs copper 10 AWG to stay near 2.02% — inside the 3% design target used for this comparison. For comparison, copper 12 AWG would drop about 7.72 V (3.22%) on the same run.

Before you pull wire

This is a voltage-drop estimate only. The conductor must also meet ampacity, temperature derating, and overcurrent rules — use the larger of the voltage-drop size and the ampacity size. Aluminum of the same size drops more, so it usually needs to go up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Sized for voltage drop using NEC Ch.9 Table 8 DC resistance. The 3% figure is a common design target from informational guidance, not a substitute for a code review.

Where this 20 amps, 100 feet scenario fits

This is a useful planning case for a modest 240 V load in a detached garage, workshop, shed, or addition where the panel is roughly 100 feet away. It is not a promise that a particular appliance belongs on a 20 A circuit; the equipment nameplate and local code decide that.

At this current, the practical choice is often whether to accept a small conductor upgrade now or live with more voltage loss for the life of the circuit. Compare the material cost against the harder-to-change parts of the job: trenching, conduit, wall access, and future load growth.

Distance changes the conductor decision

Copper recommendations for a 20 amps load at 240 V single-phase, using the same 3% target
One-way distance Suggested copper size Calculated drop
50 ft 14 AWG 2.56%
100 ft 10 AWG 2.02%
150 ft 8 AWG 1.91%
200 ft 8 AWG 2.55%

Checks specific to this project

  • Confirm that 20 A is the expected load current, not merely the breaker rating.
  • Measure the one-way route through the actual conduit path rather than straight-line distance.
  • Check whether the same raceway will contain other current-carrying conductors that require derating.
  • If the circuit may later serve a larger tool or heater, run that future load through the calculator too.

FAQ

What wire size do I need for 20 amps at 100 feet?

For voltage drop at 240 V single-phase, copper 10 AWG keeps a 20 amps load near 2.02% over 100 feet, meeting the 3% design target used on this page. Ampacity, derating, equipment instructions, and local code may require a different size — confirm with a licensed electrician.

How much voltage drop does 20 amps over 100 feet have?

On a baseline copper 12 AWG at 240 V single-phase, 20 amps over 100 feet drops about 7.72 V (3.22%). Larger conductors drop less; the calculator shows the exact figure for any size.

Is this voltage-drop sizing the same as ampacity sizing?

No. This page sizes for voltage drop only, using NEC Chapter 9 Table 8 DC resistance. The conductor must also satisfy ampacity, temperature derating, and overcurrent-protection rules. Use the larger of the voltage-drop size and the ampacity size, and verify with your local code (AHJ).

Sources & verification

Source links and page assumptions reviewed .

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. Not a substitute for a licensed electrician or your local code (AHJ). Voltage-drop sizing does not replace ampacity, temperature derating, power factor, or continuous-load checks. Verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.