Voltage drop scenario

Wire size for 50 amps at 100 feet

At 240 V single-phase, copper 6 AWG keeps a 50 amps load at about 2.05% drop over 100 feet — within the 3% design target used here. Adjust material, voltage, or phase below.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

50 amps at 100 feet: the short answer

At 240 V single-phase over 100 feet, a 50 amps load needs copper 6 AWG to stay near 2.05% — inside the 3% design target used for this comparison. For comparison, copper 12 AWG would drop about 19.30 V (8.04%) on the same run.

Before you pull wire

This is a voltage-drop estimate only. The conductor must also meet ampacity, temperature derating, and overcurrent rules — use the larger of the voltage-drop size and the ampacity size. Aluminum of the same size drops more, so it usually needs to go up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Sized for voltage drop using NEC Ch.9 Table 8 DC resistance. The 3% figure is a common design target from informational guidance, not a substitute for a code review.

Where this 50 amps, 100 feet scenario fits

This combination commonly appears while budgeting a 240 V receptacle, welder, cooking appliance, or EV-charging circuit. Those loads do not all size the same way: a receptacle rating, breaker rating, and continuous charging current are three different inputs.

Before buying wire, decide which current belongs in the calculation. For example, an EV charger on a nominal circuit may be configured below the breaker rating because charging is a continuous load. Enter the actual design current and then complete the separate ampacity and continuous-load checks.

Distance changes the conductor decision

Copper recommendations for a 50 amps load at 240 V single-phase, using the same 3% target
One-way distance Suggested copper size Calculated drop
50 ft 10 AWG 2.52%
100 ft 6 AWG 2.05%
150 ft 4 AWG 1.93%
200 ft 4 AWG 2.57%

Checks specific to this project

  • Do not automatically enter 50 A just because the receptacle face says 50 A.
  • For EV charging, use the configured continuous output and verify the equipment instructions.
  • Confirm whether the load is hardwired or cord-and-plug connected and whether neutral is required.
  • Compare copper and aluminum only after checking that every termination is listed for the chosen material.

FAQ

What wire size do I need for 50 amps at 100 feet?

For voltage drop at 240 V single-phase, copper 6 AWG keeps a 50 amps load near 2.05% over 100 feet, meeting the 3% design target used on this page. Ampacity, derating, equipment instructions, and local code may require a different size — confirm with a licensed electrician.

How much voltage drop does 50 amps over 100 feet have?

On a baseline copper 12 AWG at 240 V single-phase, 50 amps over 100 feet drops about 19.30 V (8.04%). Larger conductors drop less; the calculator shows the exact figure for any size.

Is this voltage-drop sizing the same as ampacity sizing?

No. This page sizes for voltage drop only, using NEC Chapter 9 Table 8 DC resistance. The conductor must also satisfy ampacity, temperature derating, and overcurrent-protection rules. Use the larger of the voltage-drop size and the ampacity size, and verify with your local code (AHJ).

Sources & verification

Source links and page assumptions reviewed .

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. Not a substitute for a licensed electrician or your local code (AHJ). Voltage-drop sizing does not replace ampacity, temperature derating, power factor, or continuous-load checks. Verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.