For a 50 amps copper circuit at 240 V single-phase, NEC 310.16 ampacity needs 8 AWG at 75 °C. Over 100 feet, voltage drop bumps the recommendation to 6 AWG (about 2.05% drop). Adjust the run below.
Recommended wire size
—
Enter a load, length, and voltage to size the conductor.
How the size was chosen
Ampacity needs
—
Voltage drop needs
—
Recommended (larger of the two)
—
Ampacity of recommended
—
Voltage drop of recommended
—
Governing constraint
Estimate only — not a substitute for a licensed electrician.
Ampacity from NEC 310.16 (30 °C ambient, ≤3 current-carrying conductors); voltage drop
from NEC Ch.9 Table 8. Does not model temperature/conductor-count derating, continuous
loads (125%), conduit fill, or full terminal ratings. Verify against the current NEC and
your local code / AHJ.
50 amps: the short answer
At 240 V single-phase over 100 feet,
a 50 amps copper load needs 6 AWG (about 2.05% drop). Ampacity alone would allow copper 8 AWG, but over 100 feet voltage drop pushes the recommendation up to 6 AWG to stay within the 3% target (about 2.05%).
Before you pull wire
This recommendation covers ampacity and voltage drop only, for copper at
75 °C. It does not apply ambient-temperature or conductor-count
derating, the 125% factor for continuous loads, conduit fill, or terminal ratings — any of
which can push the size up. Aluminum of the same load typically goes up one or two sizes.
Always confirm with a licensed electrician and your local code (AHJ).
Ampacity per NEC 310.16; voltage drop per NEC Ch.9 Table 8 (75 °C copper).
How to use a 50 amps wire-size result
Fifty-amp circuits are associated with ranges, welders, RV receptacles, spa equipment, and NEMA 14-50 outlets. The label is not a universal load calculation: duty cycle, continuous operation, receptacle configuration, and equipment instructions all matter.
A 14-50 receptacle can be installed for several purposes, but the connected load determines the design. Before using this recommendation, document whether 50 A is actual current, a receptacle rating, or a breaker rating. That distinction is crucial for continuous EV charging.
Code focus: The calculator compares ordinary ampacity with a 3% voltage-drop design target. It does not apply welder duty-cycle rules, range demand factors, spa requirements, or continuous-load sizing.
Why run length can change the answer
Copper sizing comparison for 50 amps at 240 V single-phase and
75 °C terminations
One-way length
Ampacity minimum
Recommended size
Governing check
25 ft
8 AWG
8 AWG
ampacity
50 ft
8 AWG
8 AWG
ampacity
100 ft
8 AWG
6 AWG
voltage drop
150 ft
8 AWG
4 AWG
voltage drop
Checks before selecting material
Identify the connected equipment before treating a 50 A receptacle as a 50 A load.
Confirm neutral and grounding needs; not every 240 V load uses the same conductor arrangement.
Check whether the equipment permits aluminum conductors before comparing material costs.
FAQ
What size wire do I need for 50 amps?
For 50 amps of copper at 240 V, NEC 310.16 ampacity at 75 °C needs 8 AWG. Over a 100 feet run, voltage drop calls for 6 AWG, so the recommended size is 6 AWG — the larger of the two. Aluminum, derating, continuous load, and local code may change this; confirm with a licensed electrician.
What size wire for 50 amps on a short run?
On a short run where voltage drop isn't a factor, 50 amps of copper needs 8 AWG at 75 °C by ampacity alone (NEC 310.16). Longer runs need a larger size for voltage drop — this page assumes 100 feet.
Does this size for ampacity or voltage drop?
Both. The conductor must carry the current (ampacity, NEC Table 310.16) and keep voltage drop within target (NEC Chapter 9 Table 8). The recommended size is the larger of the two. It still doesn't replace ambient or conductor-count derating, the 125% continuous-load factor, conduit fill, or terminal-rating checks — verify with your local code (AHJ).
Estimate only, based on NEC 310.16 ampacity and NEC Chapter 9 Table 8 voltage drop.
Not a substitute for a licensed electrician or your local code (AHJ). It does
not fully model ambient or conductor-count derating, the 125% continuous-load factor, conduit
fill, or terminal ratings. Verify against the current NEC and local code before wiring. Based on
NEC 310.16 and NEC Ch.9 Table 8.