Wire size scenario

What size wire for 200 amps?

For a 200 amps copper circuit at 240 V single-phase, NEC 310.16 ampacity needs 3/0 AWG at 75 °C. Over 100 feet, voltage drop bumps the recommendation to 3/0 AWG (about 1.28% drop). Adjust the run below.

Phase
Termination temperature rating

Recommended wire size

Enter a load, length, and voltage to size the conductor.

How the size was chosen
Ampacity needs
Voltage drop needs
Recommended (larger of the two)
Ampacity of recommended
Voltage drop of recommended
Governing constraint
Estimate only — not a substitute for a licensed electrician. Ampacity from NEC 310.16 (30 °C ambient, ≤3 current-carrying conductors); voltage drop from NEC Ch.9 Table 8. Does not model temperature/conductor-count derating, continuous loads (125%), conduit fill, or full terminal ratings. Verify against the current NEC and your local code / AHJ.

200 amps: the short answer

At 240 V single-phase over 100 feet, a 200 amps copper load needs 3/0 AWG (about 1.28% drop). Here ampacity governs: copper 3/0 AWG is needed to carry 200 amps at 75 °C, and it comfortably meets the 3% voltage-drop target over 100 feet (about 1.28%).

Before you pull wire

This recommendation covers ampacity and voltage drop only, for copper at 75 °C. It does not apply ambient-temperature or conductor-count derating, the 125% factor for continuous loads, conduit fill, or terminal ratings — any of which can push the size up. Aluminum of the same load typically goes up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Ampacity per NEC 310.16; voltage drop per NEC Ch.9 Table 8 (75 °C copper).

How to use a 200 amps wire-size result

Two hundred amps is normally service or major-feeder territory. It is included as an engineering comparison for the calculator's supported conductor table, not as a one-page recipe for a 200 A residential service.

At this current, equipment space, conductor bending radius, raceway fill, pull planning, utility requirements, and service rules can dominate the project. A result that passes the two calculator checks is still only a preliminary number for a licensed design.

Code focus: The page does not apply dwelling service-conductor allowances, utility standards, parallel-conductor rules, service grounding and bonding, or fault-current requirements.

Why run length can change the answer

Copper sizing comparison for 200 amps at 240 V single-phase and 75 °C terminations
One-way length Ampacity minimum Recommended size Governing check
25 ft 3/0 AWG 3/0 AWG ampacity
50 ft 3/0 AWG 3/0 AWG ampacity
100 ft 3/0 AWG 3/0 AWG ampacity
150 ft 3/0 AWG 3/0 AWG ampacity

Checks before selecting material

  • Coordinate meter, service, and conductor requirements with the utility and AHJ.
  • Verify that every enclosure and lug accepts the conductor material and physical size.
  • Have a qualified professional design the service or feeder rather than using the result as a material order.

FAQ

What size wire do I need for 200 amps?

For 200 amps of copper at 240 V, NEC 310.16 ampacity at 75 °C needs 3/0 AWG. Over a 100 feet run, voltage drop calls for 1 AWG, so the recommended size is 3/0 AWG — the larger of the two. Aluminum, derating, continuous load, and local code may change this; confirm with a licensed electrician.

What size wire for 200 amps on a short run?

On a short run where voltage drop isn't a factor, 200 amps of copper needs 3/0 AWG at 75 °C by ampacity alone (NEC 310.16). Longer runs need a larger size for voltage drop — this page assumes 100 feet.

Does this size for ampacity or voltage drop?

Both. The conductor must carry the current (ampacity, NEC Table 310.16) and keep voltage drop within target (NEC Chapter 9 Table 8). The recommended size is the larger of the two. It still doesn't replace ambient or conductor-count derating, the 125% continuous-load factor, conduit fill, or terminal-rating checks — verify with your local code (AHJ).

Sources & verification

Source links and page assumptions reviewed .

Estimate only, based on NEC 310.16 ampacity and NEC Chapter 9 Table 8 voltage drop. Not a substitute for a licensed electrician or your local code (AHJ). It does not fully model ambient or conductor-count derating, the 125% continuous-load factor, conduit fill, or terminal ratings. Verify against the current NEC and local code before wiring. Based on NEC 310.16 and NEC Ch.9 Table 8.